Select Committee on Education and Skills Written Evidence


Memorandum submitted by West Midlands Fire and Rescue Service

1.  INTRODUCTION

  1.1  As a metropolitan fire and rescue service deeply concerned about fire safety in schools, we welcome the Committee's decision to undertake an inquiry into Sustainable Schools. We are submitting evidence following an invitation from the Committee Chair Barry Sheerman MP to address the specific issue of fire safety and fire suppression in schools in the context of the Inquiry.

  1.2  The success of the Building Schools for the Future (BSF) Programme is directly linked to this issue of fire safety. Every year around 2,000 schools in Britain are damaged by fire. For a school to be environmentally, economically and socially sustainable, any risk of potential structural damage must be minimised. Working towards guaranteeing the longevity of the school building will ensure that the premises can "meet the needs of the present without compromising the ability of future generations to meet their own needs."

  1.3  In order to minimise the risks posed by fire, we are in favour of the mandatory fitting of automatic fire control equipment in all new build and refurbished schools. There are economic, social and environmental arguments in favour of the mandatory installation of sprinkler systems to ensure the sustainability of educational premises.

2.  THE CURRENT LEGISLATIVE AND REGULATORY SITUATION

  2.1  Currently there is no legislative requirement for the mandatory fitting of sprinklers in school buildings and there are no plans to make their fitting mandatory.

  2.2  All school buildings must comply with Approved Document B (Fire Safety) of the Building Regulations. These regulations, which are the responsibility of the Department for Communities and Local Government (DCLG), do not require schools to install sprinkler systems, but do not preclude local Authorities from doing so.

  2.3  The installation of sprinklers is similarly dealt with in Building Bulletin 100, Designing and Managing Against the Risk of Fire in Schools. This is non-statutory guidance published by the Department for Education and Skills (DfES).

  2.4  As both the DfES and the DCLG (formerly ODPM) are involved in the fire regulations and guidance relating to schools, there has been some confusion as to which department has the lead on developing Building Bulletin 100. However, former Fire and Rescue Services Minister, Jim Fitzpatrick MP, recently clarified the situation:

    "The Department for Education and Skills is in the lead in considering Building Bulletin 100 and a revision of the provision of sprinklers in schools. Its consultation will conclude later this year, and we are looking forward to that to find out whether we can move forward on this very important issue."

    Jim Fitzpatrick MP, Fire and Rescue Service Minister, response to Oral Question, (Hansard, Column 106,19 April 2006)

  2.5  After many months of indicating that a reviewed version of Building Bulletin 100 would be published, a draft version of the guidance finally underwent consultation, which closed on 18 November 2005.

  2.6  The version of the guidance that was put out for consultation did not recommend the installation of sprinklers in all schools, and stated that a risk assessment should be undertaken before any decision was made:

    "There is obviously a cost implication up to 5% of a building contract whether for new build or to upgrade existing buildings. Some school owners may decide that this is a worthwhile expenditure based on a risk assessment in their buildings in their area. Where the risk analysis highlights the fact that an ignition is probable, possibly as a result of location, the existence of certain processes or other socio-economic factors, then the fitting of automatic fire suppression systems will need serious consideration."

  NB: We estimate that the cost of installing sprinkler protection to a new school is as little as 1.8% of the total building cost. See section three.

  2.7  The DfES has yet to publish an analysis of responses to the consultation, or a revised version of the guidance. However, Schools Minister Jim Knight MP recently indicated that the analysis had been completed and would be published "shortly", whilst the Department hopes to publish the final, revised version of the guidance before the end of the year. (Hansard, Column 1214W, 14 June 2006).

  2.8  Since the consultation concluded, the DfES has continued to indicate its support for using risk assessment and cost benefit analysis to determine whether to install sprinklers in schools. For example, Schools Minister, Jim Knight MP, gave the following response to a Written Question from Joan Walley MP:

    "We work closely with colleagues in the new Department for Communities and Local Government (DCLG) and, liaising with them, we produced new draft guidance on fire safety—Building Bulletin (BB) 100, "Designing and Managing Against the Risk of Fire in Schools". It stresses the value of using risk assessments to determine what sort of fire detection and alarm systems should be used in each school, and whether or not sprinklers should be installed. While saying that a building designed in accordance with the guidance in Approved Document B (Fire Safety), which accompanies the Building Regulations, will achieve a satisfactory standard of life safety, it also suggests ways of improving property protection." (Hansard, Column 910, 16 May 2006)

  2.9  However, risk assessment or cost benefit analysis only predict the damage that would be caused by school fires in terms of the cost of material damage and the cost of the fire and rescue service attending the fire. They do not reflect the damage and disruption suffered by a local community in the aftermath of a school fire, seriously underestimating the total cost and can therefore never be accurate.

3.  THE ECONOMIC CASE FOR THE MANDATORY FITTING OF SPRINKLERS

  3.1  The Government is investing £2.2 billion in the Building Schools for the Future (BSF) programme and over the next 10-15 years there will be further funds invested in this programme to upgrade or replace all secondary schools.

  3.2  Since the year 2000, over £500 million has been lost in school fire costs alone, nearly a quarter of the Government's start up funding. This is because sprinkler suppression systems are not a requirement of school building programmes despite being recognised as one of the most effective means of combating the risk of fire.

  3.3  The BSF programme will, at the present rate, continue to lose a minimum of £100 million in fire losses per year at 2003 prices, if there is no requirement to fit sprinklers.

  3.4  Exact figures on the cost of fires to schools are difficult to ascertain. It is estimated, based on insurance claims, that the cost to schools in England and Wales stands at £100 million per year. The total year on year loss, if school fires continue to rise at the present rate, up until 2016 is estimated at 3 billion. However, the true cost is likely to be significantly higher as insurance costs cannot reflect the level of disruption, social impact, environmental damage or the effect on learning that a fire causes.

  3.5  If sprinkler systems were a requirement of the BSF programme, there would be a return on the Government's initial investment in the programme in 10 years time. As more schools are fitted with suppression systems this gain will increase, as the amount of losses attributed to fire will decrease year on year.

  3.6  The cost of installing sprinkler protection to a new school is as little as 1.8% of the total building cost and it is estimated that even a retrofitted system will pay for itself in savings from fire damage within eight to 10 years. (The cost of installing a sprinkler system is roughly equivalent to carpeting the same building.)

  3.7  Furthermore, many insurers offer discounts for sprinkler protected school properties. These discounts are typically around 15% of the building and contents premium and would greatly assist in recouping the cost of installing a sprinkler system.

4.  THE SOCIAL AND ENVIRONMENTAL CASE FOR THE MANDATORY FITTING OF SPRINKLERS

  4.1  The economic loss does not take into account the effects on the environment due to pollutants from fire, smoke and water run off, or the social loss to local communities. This is particularly significant as the BSF programme aims to make school buildings more community friendly with extended opening hours for community activities to take place in them.

  4.2  Sprinklers reduce building damage and have the potential to increase the lifespan of a building. Fire statistics from the USA indicate a 90% reduction in fire damage costs where sprinklers are in place. Buildings that have a fire are usually uninhabitable afterwards and may have to be demolished. However, a sprinkler protected room can usually be back in use within a few hours and the rest of the building is usually unaffected.

  4.3  The provision of sprinkler systems in a building allows greater flexibility in the building design with the effect of reducing costs. Sprinklers can save on building costs because under the building regulations larger compartment sizes may be constructed. Reduced boundary and extended travel distance to fire exits are allowed. A reduction in structural fire protection is also possible.

  4.4  Sprinklers help to protect the environment by controlling a fire in its early stages, preventing airborne pollution and water run-off.

  4.5  Sprinklers save water. Statistics show that the widespread use of sprinklers could save up to 96% of the 5.6 billion litres of water used annually in the UK to fight large fires.

5.  CASE STUDY—SCHOOL FIRE AT A WEST MIDLANDS SCHOOL

  5.1  In May 1999 West Midlands Fire Service was called to attend a school fire. The severity of the fire was such that it took 100 firefighters over 22 hours to control.

    —  40,000-50,000 litres of water were used to douse the flames.

    —  100-199 sq metres of school property were damaged.

    —  The fire caused over £80,000 worth of material damage.

  The fire caused the whole school to be closed for several days and resulted in severe disruption for students and the wider community.

  5.2  If the school had installed sprinklers, the fire would have been controlled immediately and no significant damage would have occurred.

  5.3  After the fire, Wormald Fire Systems were invited to provide a quotation for installing a sprinkler system throughout the school.

  5.4  They indicated that the cost of retro-fitting the system would be £31,071 if installation took place during school holidays.

  5.5  The maintenance costs, once the system had been installed, were estimated at just £140 per annum. This is much lower than typical annual maintenance of passive fire protection measures such as fire doors and escape routes.

6.  CONCLUSION

  6.1  It is our contention that a sine qua non of Sustainable Schools must be their ability to survive physical external threats such as fire and that the installation of sprinkler systems is the most cost effective way of achieving this. The Select Committee Report should advocate Government action to mandate the progressive fitting of sprinklers in school buildings.

  6.2  New measures are required to reduce the risk of fires in educational buildings and to reduce the level of damage caused. DCLG figures show that school fires cost the economy £52 million in 2004 (Hansard, Column 1218, 14 June 2006). This figure does not reflect the disruption, loss of schoolwork, decline in educational attainment and damage to the local community that can result from school fires.

  6.3  The West Midlands Fire Service believes that the Government should require the mandatory fitting of sprinklers in all new-build and refurbished schools, and should ensure that the revised version of Building Bulletin 100 recommends the use of sprinklers.

  6.4  We appreciate that it is not realistic for every school to be retro-fitted with immediate effect. However, it should be mandatory to install sprinklers in all new-build schools under the BSF programme. Educational premises undergoing refurbishment should also be obliged to retrofit. Other schools should be encouraged to consider the installation of a sprinkler system at the earliest opportunity.

  6.5  We should be happy to elaborate further on this issue and provide any additional information that the Committee would find helpful.

June 2006





 
previous page contents next page

House of Commons home page Parliament home page House of Lords home page search page enquiries index

© Parliamentary copyright 2007
Prepared 9 August 2007