  4140. What we have here is that part of the Phase 3, Stage 1 Settlement Assessment Report in respect of 17 to 25 Wilkes Street.[27] We have put this up because my understanding is that Mr Wheeler owns a property within this group and this page is summarising findings in relation to structural sensitivity, sensitivity of particular features and finishes, and other matters in relation to that building. Can you just tell the Committee what you get from this information please?

  (Professor Mair) Yes, what I described before lunch was essentially the engineering analysis part which is shown here and I explained that that led to the conclusion for this particular set of buildings that the maximum tensile strain was estimated to be 0.024 per cent which itself is a very conservative estimate, and that would put it in the `negligible damage' category, zero. That is the engineering part of the assessment as far as settlement and potential tensile strain is concerned, but there is also, and this is of particular relevance for listed buildings, the question of the sensitivity of the building in terms of two aspects, and I will enlarge upon these. One aspect is divided really into two parts, the sensitivity of the structure, and, by that, I mean the sensitivity of the building to tolerate movement without significant distress, and there is an additional consideration given to that which itself has a score. There is a second part which is the sensitivity of particular features and finishes within the building and the question as to how vulnerable or sensitive those features are, and that also has a score. The table shown near the bottom of this page summarises the position and, first of all, you will see the sensitivity, the `predicted damage' category, which is the third line down, and there you will see the score zero, which corresponds to the `negligible' category in terms of the engineering analysis leading to the tensile strain. You will see that there are two other scores, one, the sensitivity of the building structure, which in this case has given the score one, and I will elaborate a bit more about what the significance of the scores are, and there is also the question of the sensitivity of any special or vulnerable features and finishes, which in this particular case has given the score zero. The total of the three scores are then added up to give the final total score which in this case is one, and again the significance of that I will go on to describe, but this is really by way of introducing the point that, in the case of listed buildings, there are these two extra criteria which are taken into account, the sensitivity of the structure as a whole and the sensitivity of any particular features and finishes within it.

  4141. Now, in order to explain those two matters, that is to say, the structure and particular features, we need to go to a table which is to be found at page 11 of information paper D12. We have got that up on the screen.[28] My Lords, it is in your red pack of information papers, as you saw yesterday, in the D divider, so you have hard copies of it as well. I am so sorry, this is not the right one, is it?

  (Professor Mair) I think you need table 2 which is the next page.[29] This table explains in some more detail what I have just been describing. This is, if you like, the special scoring system for the sensitivity of listed buildings and there are two separate groups. The left-hand column is the sensitivity of the structure as a whole to ground movements and sensitivity to interaction with its neighbouring buildings, and the scoring system for that is zero, one or two in terms of really increasing sensitivity or severity, so, if it gets a zero score, that would be saying that it is a masonry building with lime mortar, not surrounded by other buildings, with uniform façades with no particular large openings. If that was the case, that would get the score zero. If the buildings were of delicate structural form or buildings sandwiched between modern framed buildings, which themselves are much stiffer, and perhaps itself the building has one or two more significant openings, that would make it somewhat more vulnerable, so it would get the score of one. Then, in cases where the buildings which, by their own structural form, will tend to concentrate all of the movements in one location, that is potentially of more concern and that would get the score of two. That is how the sensitivity of the structure in terms of the overall way it might respond gets scored. Then, on the right-hand side there is a separate grouping which is to do with the sensitivity to movement of particular features within the building and again the scoring system is applied so that, in cases where there were no particular sensitive features, if that judgment was made, there would be a score of zero. If there were brittle finishes, for example, faiences or tight-jointed stonework which are most susceptible to movement, even small movements, and difficult to repair, then they would be given the score of one. If there were finishes, and this is a most important point, which, if damaged, would have a significant effect on the heritage of that building, for example, cracks through frescos, that kind of example, that would get the higher scoring of two. The whole purpose of this additional sensitivity scoring for listed buildings is to take into account the heritage aspects of the buildings in question. I was going to ask, Mr Mould, if we could perhaps go back to that front-sheet example for 17-25—

  4142. Just before we do, my Lord, Lord Colville, put the question just before the short adjournment in relation to cornicing and we see that that, I think, is a feature which would fall to be considered on the right-hand side of the table.

   (Professor Mair) Yes, that is correct.

  4143. Insofar as it was a particularly sensitive feature, it would fall within the right-hand side of the table, and one can see that the most vulnerable, if I can put it this way, category in relation to the right-hand side of the table, category two, focuses upon elements which are of significance to the heritage of the building. Do you see that?
  (Professor Mair) That is exactly correct.

  4144. MR MOULD: I do not know if you feel able to comment on this but if one was focusing, for example, on a building which had corniced ceilings is it right that one of the questions one would need to ask as to where the existence of that feature placed the building in this table, would be whether that element of the building was or was not of importance to its heritage value?

  4145. (Professor Mair) Yes, I think what you are asking me is the significance of the difference really between the category one and the category two for the right hand column, for finishes?

  4146. Yes.

   (Professor Mair) I think that if there was something that was identified clearly as being part of the heritage of the building, such as a very important fresco or some feature like that, which was an identified aspect of its heritage, and if that was present then that would be appropriate to be scored under the category two.

  4147. But the corollary is, if one thinks of buildings of more than a certain age cornice ceilings are a relatively typical feature of many buildings older than the 20th century, for example, and features of that kind, which, if you will, are no more than typical, the question would need to be asked, would it not, whether such features, albeit present in the building under consideration, did or did not merit any higher, for example, than category one in this table?

   (Professor Mair) Yes, they would not merit any higher category than category one and arguably they could even be in category zero.

  4148. MR MOULD: I am raising points which are moving towards the expertise of Alan Baxter, but I think it is helpful to flag these points up with the Committee and I am grateful to you for your assistance on that.

  4149. LORD YOUNG OF NORWOOD GREEN: Yesterday there was a lot of focus from one of the Petitioners, Mr Wheeler, on the fact that he questioned, if you like, the integrity of the assessment that had been made, the scores, because there had not been in every case an internal survey. When I look at this background document and how you allocate the scores it would seem to be that that is necessary. But that may be an assumption too far that I am making; can you clarify that?

  4150. MR MOULD: My Lord, forgive me, but we are going to come on to explain the significance of the inspections that we carried out with this process in a very few moments. Would it be convenient to deal with it that way because we have a logic here and I would like to stick with it, if we may? If we have not dealt with it to your satisfaction when we come to it, then by all means we will deal with any further points arising.

  4151. CHAIRMAN: If you have not dealt with it by the time you come to the end of Professor Mair's evidence I am going to ask anyway.

  4152. MR MOULD: I did not think we would get away with it!

  4153. LORD YOUNG OF NORWOOD GREEN: And it will be more penetrating!

  4154. MR MOULD: I am very grateful for that indulgence. Professor Mair, I took you a little out of your way, for which I apologise, but I hope it was helpful. Now we want to go back to page 58, is that right?

   (Professor Mair) That is right.

  4155. Is that right?

   (Professor Mair) That is the page, I think just briefly, and then I think we will need to go on to another one. This is the summary page—we will go into more detail shortly—for this particular structure, which results in the total score of one, there essentially being three elements—the predicted damage category from the calculation of the engineering strain, the tensile strain; and then the other two categories, the sensitivity of the building as a structure and then the sensitivity of features or finishes.

  4156. If we look at the top of the page and with our minds cast back to the table you showed us a moment ago, in relation to the left hand side of the table we can see under the heading "sensitivity of structure" the score of one given there and an explanation for that. Then as regards to the right hand side we can see the issue of sensitivity in particular of features and finishes is dealt with, a score of nil. And we know that Lord Young wants us to explain how that is arrived at given the level of inspection that was undertaken. So we go on then to page 58.[30]

  (Professor Mair) The heading of this page is "historic buildings and features" and this really sets out a lot of the details of the building in terms of its heritage. It first and most importantly makes the point that the date of the building is 1723—we see that four lines down—which sets the scene for the experts who are assessing the type of building and its vulnerability to movement. The very fact that it is 1723 immediately flags up that we are talking here about early Georgian buildings. A bit further down you see other important features. The site of the building is important; it is shown here to be three stories plus cellars, plus the weavers' attics. You cannot quite see those in the photograph but above the building there is an attic as well—or there are attics along the building. Then in much more detail—and I will not go through all of what is written here—this is the assessment of the building in terms of its description of what kind of building it is—any special features, how it has been constructed—and below that paragraph you will see the title, "significant or potentially vulnerable features", and there are various points listed down here about that.

  4157. MR MOULD: Just in relation to the question of height, Mr Wheeler had a point on that yesterday. Can you explain to the Committee what are the significant factors as regards height for the purposes of this assessment?

  4158. CHAIRMAN: These are all things you can see from the outside, are they? I would expect so.

   (Professor Mair) These are principally the things that could be seen from the outside, that is correct, yes.

  4159. LORD BROOKE OF ALVETHORPE: Yesterday it was claimed that the report did not in fact give the true height of the building and that this would have an impact that was not being recognised.

   (Professor Mair) I can comment on that. I think actually that comment was made about this row of buildings, if I am not mistaken.



27   Crossrail Ref: P23, 17-25 Wilkes Street, listed Building Assessments, Phase 3 Iteration 1 Reports, Mott MacDonald (TOWHLB-XR5A-056) Back

28   Crossrail Information Paper D12-Ground Settlement, Table 1, http://billdocuments.crossrail.co.uk (LINEWD-IPD12-011) Back

29   Crossrail Information Paper D12-Ground Settlement, Table 2, http://billdocuments.crossrail.co.uk (LINEWD-IPD12-012) Back

30   Crossrail Ref: P23, 17-25 Wilkes Street, Historic Building and Features, Mott MacDonald (TOWHLB-XR5A-058) Back


 